1. It can measure the resistive current of three-phase lightning arresters simultaneously.

2. It measures the total current, resistive current and its harmonics, power frequency voltage, active power, and phase difference of zinc oxide lightning arresters.

3. It has anti-interference and automatic compensation functions.

4. It has functions such as fundamental peak output of resistive current and side-phase correction.

5. It features a liquid crystal display screen and full Chinese menu operation, making it easy to use.

6. It is equipped with a rechargeable battery, calendar clock, and micro printer.

7. It can store measurement data.


Product Technical Parameters


Edit

1. Current measurement range: 0 to 10mA (peak)

2. Voltage input range: 10 to 200V (peak, reference voltage input)

3. Maximum allowable error: ±(reading ´3% ±1 digit) (under wired mode conditions)

4. Power supply: AC 220V or internal battery

Continuous working time is less than 6 hours, battery charging takes more than 6 hours

6. Dimensions: (length) 325mm×(width) 275mm×(height) 145mm

7. Weight: 3kg (excluding accessories)



Resistive Current Measurement Mode


Edit

There are three resistive current measurement modes: wired mode, wireless mode, and induction mode.

Generally, wired mode is selected for measurement to ensure accuracy. The other two modes are for reference only.