Dielectric Loss TestThis tester is designed for testing the volt-ampere characteristics, transformation ratio, and polarity discrimination of current transformers. It uses high-efficiency, low-consumption quality materials and a specially wound booster. A microprocessor performs data acquisition, analysis, and storage, and a built-in micro printer prints test data curves. When measuring CT transformation ratio, it can automatically calculate the ratio. This device is lightweight, easy to operate, and portable, making it suitable for laboratory and field use.
◇ Main Technical Parameters ◇
1. Input voltage: AC 220V or 380V, 50Hz, automatic input voltage recognition
2. Operating ambient temperature: 0~40℃
3. Output voltage:
When input AC 220V, output 0~500V~1000V
When input AC 380V, output 0~1000V~2000V
Current: maximum instantaneous current, 600A when measuring transformation ratio
When input AC 220V, output 0~400A
When input AC 380V, output 0~600A
15A when testing volt-ampere characteristics
4. Digital voltmeter measurement range: 0~9999V; resolution: 0.1V
When used as current display: 0~9.9A; resolution: 0.1mA
5. Digital ammeter measurement range: 0~3000A, resolution: 0.01A
6. Error: I≤1%, U≤1%
7. When measuring CT transformation ratio, it can automatically calculate the ratio value and print the data and calculation results
8. When testing volt-ampere characteristics, it stores and prints 20 sets of current and voltage values and the volt-ampere characteristic curve
9. Dimensions: 470mm×340mm×260mm
10. Weight: 23kg


