Three-phase high current generator I



The SLQ-III-6300A temperature rise three-phase high current generator is a specialized device designed and manufactured for power departments and electrical equipment enterprises to test various electrical equipment for current load tests and temperature rise tests.

  This product, the three-phase high current generator 6300A series, adopts an integrated structure and serves as a three-phase continuous high current AC power source. It features a special production process for balanced three-phase current phase difference, with electric adjustment for stepless current regulation, balanced rise of three-phase current, wide load variation range, accurate current display, reliable operation, simple operation, and safety. The three-phase high current generator is an ideal device for current rise or temperature rise tests in industrial and mining enterprises.



II. Main Technical Parameters:



























































Input Power Supply



Three-phase four-wire 380V/50Hz



Temperature rise three-phase high current generator 6300A series output current



Output three-phase 0~6300A, with functions such as current start, stop, simultaneous three-phase current rise, simultaneous three-phase current decrease, single-phase independent current rise, single-phase independent current decrease, and pre-timing, to solve the problem of three-phase imbalance.



Output Capacity



Not less than 150KVA  three-phase



Output Voltage



0~10VAC standard sine wave 



Timing Function



 



1. Equipped with timing function; after reaching the preset time, the device stops working.



Current Stability



1. When the grid fluctuation is 1%, the three-phase high current generator output current below 500A has a stability of 0.5%FS, i.e., fluctuation within ±5A.



 When output current is 500A to 800A, stability is 1%FS, i.e., fluctuation within ±10A.



 When output current is 800A to 6300A, stability is 2%FS, i.e., fluctuation within ±20A.



2. When the grid is stable, the three-phase high current generator output current stability is 0.5%FS, i.e., fluctuation within ±5A.



3. The above current stability is measured after the device has been in use for a period and reached thermal equilibrium.



Current Accuracy



Accuracy class 0.5, 0.5%FS, i.e., ±5A.



Current Adjustment Method



Manual adjustment



Current Resolution



1A, starting current from 10A



Three-phase high current generator protection function



Three-phase overcurrent protection design



Display Requirements



Both current and voltage are displayed with LED digital displays



Accessory Requirements



Equipped with connecting wires



Other Requirements



Split type




III. Operating Environment:



1. Working power supply: 380V ±10% 50HZ

2. Ambient temperature: —10℃~40℃

3. The product 6300A temperature rise three-phase high current generator should be placed in a location free from gas vapor that seriously affects transformer insulation, chemical dust, dirt, and other explosive media.



IV. Working Principle:



After connecting the working power supply to this series of products, the temperature rise three-phase high current generator 6300A series adjusts the output voltage of the voltage regulator to obtain the required high current for testing. The working principle diagram is as follows: