Transformer Turns Ratio and Vector Group Tester
Edit
★ A. Light weight, strong load capacity!
★ B. Output current: Three-phase absolutely balanced, waveform is standard sine wave
★ C. Three-phase simultaneous adjustment, or each phase individually adjustable
Note: Three-phase high-current generator (current can be increased according to user requirements).
Functional features: (1) Imported iron core, small size and light weight
(2) 0.5 class digital true RMS meter
(3) No external standard CT and ammeter required
(4) Coarse and fine adjustment with zero position indicator, power supply 220/380/66V
The high-current generator uses an energy-saving high-permeability current booster, and the instrument is indicated by a true RMS 0.5 class digital meter. It is equipped with a digital electric stopwatch to meet time measurement requirements. It has the characteristics of large output power, strong overload capacity, clear readings, and flexible movement. It is suitable for power system technicians to test current transformers, protection devices, and secondary circuit current tests.
Input power: AC 220V 50Hz.
Rated output: 0-1500A, 2000A, 3000A, 4000A, 5000A, 8000A, 10000A.
Output terminal open-circuit voltage ≥6V.
Dimensions: 540X300X250 (mm) III. Main technical parameters of the special three-phase high-current generator for temperature rise: 1) Input: AC 50Hz, 220V.
2) Can balance output 0—customer required--three-phase AC high current; can be smoothly and continuously adjusted, accuracy higher than 0.5 class; output current is standard sine wave
3) Output current mode: true RMS continuously adjustable
4) Output waveform: standard sine wave
5) Output open-circuit voltage: ≥6V
6) Current stability: 0.2%.
7) Current waveform distortion THD 1% design standard is far higher than national standard <GB14048.2-14>.
8) Protection settings: overcurrent, overvoltage
9) Insulation withstand voltage: 1800/AC 1MIN, insulation class: Class B
10) Can measure the current action time of the tested element. And can synchronously record and lock the action time. Automatically distinguish normally open and normally closed contacts. Time measurement range: 0.001S---9999.999 S, accuracy; 0.001S (optional).
11) The design adopts advanced single-chip microcomputer control technology, making the instrument simple and convenient to operate. The entire testing process is reliable and stable, with direct and fast readings. The application of high-precision sensors effectively ensures the accuracy of test data. The whole machine test unit includes: high-precision millisecond timer, true RMS ammeter, current sensor (imported), voltage regulator, high-power current booster (imported material), microcomputer controller, printing function (optional function), etc.
12) Working environment: -10℃-----60℃
13) Weight: 12-15 KG