The dielectric loss insulation test can effectively detect overall moisture, deterioration, and local defects in the insulation of electrical equipment. It is widely used in electrical manufacturing, electrical equipment installation, handover, and preventive tests.



This instrument adopts variable frequency power supply technology, utilizing microcontrollers and electronic technology for automatic frequency conversion, analog-to-digital conversion, and data processing, achieving strong anti-interference capability, fast test speed, high accuracy, and easy operation.



The variable frequency power supply uses a high-power switching power supply, outputting pure sine waves at 45Hz and 55Hz, automatically boosting voltage, providing up to 10kV; it automatically filters out 50Hz interference, suitable for on-site testing in environments with high electromagnetic interference such as substations.



: Dielectric loss tester, anti-interference dielectric loss tester, automatic dielectric loss tester, variable frequency dielectric loss tester, variable frequency dielectric loss tester, anti-interference dielectric loss tester, automatic dielectric loss tester



 



Product Parameters Product Parameters



Technical Parameters










































































Measurement Range Capacitance Value 3pF ~ 60000 pF/10kV, 60pF ~ 1μF/0.5kV
Dielectric Loss Range 0 ~ 100% unlimited, Resolution: 0.001%
Automatic identification of capacitance, inductance, and resistance test objects
Maximum Error Capacitance Accuracy ±(1.0%×reading ±1 pF)
Dielectric Loss Accuracy ±(1.0%×reading ±0.04%)
Resolution Capacitance Resolution Minimum distinguishable 0.001 pF
Dielectric Loss Resolution Minimum distinguishable 0.001 pF
Test Current Range 10μA ~ 5A
Internal High Voltage Set Voltage Range 0.5 ~ 10kV
Maximum Output Current 200mA
Test Frequency 50Hz single frequency, 45/55Hz automatic dual frequency conversion
Power Supply 180V ~ 270VAC, 50Hz/60Hz ± 1% (mains or generator supply)
Working Environment Ambient Temperature 0 ~ 40℃
Ambient Humidity ≤ 90%RH, non-condensing
Dimensions 465×350×360mm 3
Weight 27.6kg



Note:

1. The product appearance is subject to the actual product. Technical parameters and models are subject to change without prior notice. Any unauthorized use or copying will be prosecuted.