Measurement of transformer capacity, no-load current, no-load loss, short-circuit voltage, and short-circuit (load) loss

Working power supply Input voltage 185Vac~250Vac

Allowable input voltage 85Vac~264Vac

Frequency 50/60Hz

Input power 40VA

AC voltage Range 10~650V

Resolution 0.001V

Accuracy 0.2%±0.001V

AC current Range 0.5~60A

Resolution 0.001A

Accuracy 0.2%±0.001A

Resolution 0.001Hz

Accuracy 0.2%±0.001Hz

Power Range 0~39kW

Resolution 0.001kW

Accuracy <±0.5%(CosΦ>0.1),±1.0%(0.02<CosΦ<0.1)



LCD Panel



The LCD display interface mainly consists of eleven screens, including the main menu and ten functional interfaces, which are described in detail below.



1. Main Menu Interface



Upon power-on, the instrument enters the main menu, as shown in Figure 3:



The main menu has ten options: Capacity Test, Parameter Settings, Active Load, Single-Phase No-Load, Three-Phase No-Load, Single-Phase Short-Circuit, Three-Phase Short-Circuit, Result Query, Electrical Parameters, and Harmonic Analysis. When the cursor points to a function option, that option is displayed in reverse color. In Figure 4, the selected item is 'Capacity Test'. Use the up, down, left, and right keys to change the cursor position. Press the Enter key to enter the selected function display. The bottom line is the prompt line, showing the current date and time, the internal battery voltage amplitude, and the remaining battery percentage, allowing timely monitoring of the battery status to know whether charging is needed to avoid being unable to work on site due to insufficient charge.