Lightning Protection Component Tester
Accuracy: Cx: ±(Reading×1%+1pF)
tgδ: ±(Reading×1%+0.00040)
Anti-interference Index: Frequency conversion anti-interference, can still achieve the above accuracy under 200% interference
Capacitance Range: Internal applied high voltage: 3pF~60000pF/10kV 60pF~1μF/0.5kV
External applied high voltage: 3pF~0.5μF/10kV 60pF~10μF/0.5kV
Resolution: Up to 0.001pF, 4 significant digits
tgδ Range: Unlimited, resolution 0.001%, automatic identification of three types of test objects: capacitor, inductor, resistor.
Test Current Range: 10μA~1A
Internal Applied High Voltage: Set voltage range: 0.5~10kV Voltage resolution: 1V Accuracy: 2%
Maximum Output Current: 200mA
Voltage Regulation Method: Continuous smooth adjustment
Test Frequency: 45, 50, 55, 60, 65Hz single frequency
45/55Hz, 55/65Hz, 47.5/52.5Hz automatic dual frequency conversion
Frequency Accuracy: ±0.01Hz
External Applied High Voltage: Maximum test current 1A for normal wiring, power frequency or variable frequency 40-70Hz
Maximum test current 10kV/1A for reverse wiring, power frequency or variable frequency 40-70Hz
CVT Self-Excitation Method Low Voltage Output: Output voltage 3~50V, output current 3~30A
Measurement Time: Approximately 36s, depending on measurement method
Input Power: 180V~270VAC, 50Hz±1%, powered by mains or generator
Computer Interface: Standard RS232 interface
Printer: Weihuang A7 thermal micro printer
Ambient Temperature: -10℃~50℃
Relative Humidity: <90%
Dimensions: 460×360×350mm
Instrument Weight: 28kg
35kV Variable Frequency Dielectric Loss Tester - Level 4 Contractor Equipment List Technical Parameters:
High Voltage Output: 0.5~10kV, each step increases by 500V, total ten steps, Capacity: 1000VA
Accuracy: tgδ: ±(Reading*1.0%+0.08%)
Cx: ±(Reading*1.5%+5PF)
Resolution: tgδ: 0.01% Cx: 1pF
Measurement Range:
0.1% < tgδ < 50%
3PF< Cx < 60000PF
At 10KV, Cx≤30000PF
At 5KV, Cx≤60000PF
Power Supply Harmonic Adaptation Capability: ≤3%
Introduction:
One operation, the microcomputer automatically completes the entire measurement process. It is a dielectric loss measurement device. The variable frequency anti-interference dielectric loss tester can also
Safety Measures:
1. Before using this instrument, be sure to read this manual carefully.
2. The operator should have general knowledge of electrical equipment or instruments.
3. The instrument should avoid severe vibration.
4. The instrument must be reliably grounded to prevent electric shock hazards.
5. After the test, press the reset button, turn off the power switch, and strictly prohibit disassembling test cables or replacing oil samples while energized.
6. Daily maintenance of the instrument must be carried out without power supply, otherwise high voltage danger