High Current Temperature Rise Device Introduction:



Adopting imported high magnetic permeability materials, with exquisite design, featuring compact size, strong electric dynamic resistance, and ease of use, this series of high current generators is essential equipment for places requiring high current in electrical debugging across various industries. It is applied in power plants, substations, electrical appliance manufacturing plants, and scientific research and laboratory units, operating under short-time or intermittent duty. It boasts characteristics such as small size, light weight, and good performance.



High Current Temperature Rise Device Detailed Description:



As a professional manufacturer with professional production technology, we produce professional quality products. Shanghai Baishi Electrical Technology Co., Ltd. is one of the few production-oriented enterprises in East China. Choosing Baishi means choosing peace of mind.



The high current generator is specially designed and manufactured for electrical equipment tests in power departments and industrial and mining enterprises, such as current load tests and temperature rise tests for various switches, current transformers, and other electrical equipment. This series of high current generators adopts integrated or split structures depending on product size and weight, featuring stepless output current adjustment, balanced current rise, wide load variation range, reliable operation, simple operation, and safety. It is an ideal device for current boosting or temperature rise tests in industrial and mining enterprises.



Main Features:



1. Load testing, capable of instantaneous output as required.

2. Stable output current, clear instrument indication, convenient for data recording and observation of the tested object.

3. Output current is divided into gears, each gear size smoothly adjustable, with easy rise and fall control and continuous uniform adjustment.

4. Small size, light weight, flexible movement, and convenient operation, suitable for on-site use.



Technical Specifications:



1. Input power: AC: 220V-25A, 50Hz

2. Output current: AC: 1000A, 5V or 500A, 10V

3. Output current waveform distortion: ≤5%

4. 4 1/2 LCD digital display, range: 0~1000A, resolution: 0.1A,

Accuracy: ±0.5%

5. Operating environment: temperature -10-40°C, relative humidity <80%

6. Dimensions: 402X232X245mm

7. Weight: 30Kg



Usage Methods and Precautions:



1. Connect the working circuit according to the electrical schematic diagram. The transformer casing and operation console must be properly grounded.



2. Connect the power supply, and the green indicator light on the operation console will illuminate. Press the start button, and the red indicator light of the high current generator from the genuine manufacturer will illuminate, indicating that the current booster is ready to boost current.



3. Rotate the voltage regulator evenly clockwise, paying attention to the output current indication on the operation console until the required high current is reached. To ensure testing accuracy, a standard ammeter can be connected in series at the instrument terminals.



4. During the test, if any abnormal phenomenon is found, immediately cut off the power supply, and only after identifying the cause can the test be continued.



5. After the test, the voltage regulator must be returned to zero, press the stop button to cut off the power supply, and disconnect the working power before removing the test wiring to ensure safety.