2. Turn on the power switch. The display will show self-test 1; self-test 2; self-test 3; passed, indicating the instrument is performing self-test. Finally, it will display the ratio, tap percentage, vector group, and the information display (error display) will show "Self-test passed", indicating the instrument is normal and ready for the next step.
3. Press the
4. Use the tap adjustment key to adjust the tap position. Each press of this key moves the tap value by one tap step. If pressing the tap adjustment key has no response on the tap display, it means the tap step has not been set. In this case, press the parameter key to set the tap step.
5. Measurement
a. Three-phase continuous: Press the
b. Single-phase: Press the
6. Printing
a. If printing is required, you must press the record key before the measurement operation. The key light turns on, and the instrument enters the automatic recording state, automatically recording data for each subsequent measurement operation. If the power is cut off, and if you use the three-phase continuous function for measurement, the instrument automatically records, so there is no need to press the
b. Press the print key, the screen displays "Printing", and after a moment, the screen displays "Print complete". If you press any key during printing, the screen displays "Print aborted", allowing you to exit printing midway. If there is no data in memory, pressing the print key will cause both the print and record key lights to flash, and the screen displays "Memory empty", so printing cannot be performed.
c. Of course, if the previous test data does not need to be retained, clear the data before the measurement operation. Press the
7. Use of Other Function Keys
a.
b.
c.
d.
e. Numeric keys: The numeric keys are multi-function keys, effective when the
Usage Precautions
1. Do not touch the test object during measurement.
2. If the test leads are short-circuited or the high and low voltage connections are reversed, the fuse will blow. After the fuse blows, if you attempt measurement, the display will show "Measuring, please wait!" and then stop. Turn off the power, replace the fuse with one of the same rating, and retest.
3. Ensure good contact of connections, and the instrument should be properly grounded!
4. The working place of the instrument should be far from strong electric fields, strong magnetic fields, and high-frequency equipment. The power supply interference should be as small as possible; it is advisable to use lighting circuits. If the power interference is still significant, an AC purified power supply with a capacity greater than 200VA can be used to power the instrument.
5. If the LCD display becomes disordered, all keys are unresponsive, or the measured values differ greatly from actual values during operation, press the reset key or turn off the power and restart the operation.
6. If the display shows no characters or the characters are too faint, adjust the brightness potentiometer to a suitable position.
7. The instrument should be stored in a dry and ventilated place.