2. Turn on the power switch. The display will show self-test 1; self-test 2; self-test 3; passed, indicating the instrument is performing self-test. Finally, it will display the turns ratio, tap percentage, and vector group from the last test, and the information display (error display) will show "Self-test passed", indicating the instrument is normal and ready for the next step.
3. Press the
4. Use the tap adjustment key to adjust the tap position. Each press of this key moves the tap value by one tap step. If pressing the tap adjustment key has no effect on the tap display, it indicates that the tap step has not been set. In this case, press the parameter key to set the tap step.
5. Measurement
a. Three-phase continuous: Press the
b. Single-phase: Press the
6. Printing
a. If printing is required, you must press the record key before the measurement operation. The key light turns on, and the instrument enters the automatic recording state, automatically recording data from each subsequent measurement operation. When the power is turned off, if the three-phase continuous function is used for measurement, the instrument automatically records, and there is no need to press the
b. Press the print key, the screen displays "Printing", and after a moment, the screen displays "Print completed", indicating printing is done. If any key is pressed during printing, the screen displays "Print aborted", allowing you to exit printing midway. If there is no data in memory, pressing the print key will cause the print key light and record key light to flash simultaneously, and the screen displays "Memory empty", indicating printing is not possible.
c. Of course, if previous test data does not need to be retained, clear the data before the measurement operation. Press the
7. Use of Other Function Keys
a.
b.
c.
d.
e. Numeric keys: The numeric keys are multi-function keys, effective when the