Test Set Features
◆ Simple operation, Chinese display, printing
◆ Easy to use, no conversion needed
◆ The variable frequency dielectric loss test set comes with high voltage, strong anti-interference capability, and short test time.
Test Set Characteristics
Test Set Parameters
| 1. | Due to the adoption of frequency conversion technology, accurate measurement can be ensured under strong electric field interference. |
| 2. | The instrument uses a Chinese menu operation, and the microcomputer automatically completes the entire measurement process. |
| 3、 | This instrument is also suitable for measuring the tgδ and capacitance of high-voltage electrical equipment in workshops, laboratories, and scientific research institutions; it is more convenient, simple, and accurate for testing the loss of insulating oil. |
| 4、 | This instrument can measure ungrounded or directly grounded high-voltage electrical equipment using the positive or reverse wiring method. It can also measure the tgδ of capacitive voltage transformers and the main capacitances C1 and C2. |
| 5、 | The instrument is equipped with a high-voltage step-up transformer and has safety protection measures such as zero-crossing closing and lightning protection. During the test, high voltages of different levels from 0.5KV to 10kV are output, making operation simple and safe. |
1、High voltage output: 0.5 ~10kV, each step increases by 500V, with a total of 20 steps
High voltage output cable can be used on the ground
Three frequencies: 45Hz, 50Hz, 55Hz
2、Capacity: 1500VA
3、Accuracy: tgδ: ±(reading*1.0%+0.08%)
Cx: ±(reading*1.5%+5PF)
4、Resolution: tgδ: 0.01% Cx: 1pF
5、Measurement range: 0.1% < tgδ < 50%
3PF< Cx < 60000PF
At 10KV, Cx ≤30000PF
At 5KV, Cx ≤60000PF
6、Power supply: AC 220V士10% 50士1Hz
7、Harmonic adaptation: ≤3%
8、Operating conditions: -15℃-50℃, relative humidity <80%
9、Dimensions: 460(L)×335(W)×340(H)
10、Weight: 30 kg
Working principle:
After the variable frequency dielectric loss test set starts measurement, the high voltage set value is sent to the variable frequency power supply. The variable frequency power supply uses a PID algorithm to slowly adjust the output to the set value. The measurement circuit sends the actual high voltage to the variable frequency power supply, fine-tunes the low voltage, and achieves accurate high voltage output. According to the positive/reverse wiring setting, the measurement circuit automatically selects the input and switches the range based on the test current. The measurement circuit uses Fourier transform to filter out interference, separates the fundamental wave of the signal, performs vector operations on the standard current and the test object current, calculates the capacitance from the amplitude, and calculates tgδ from the phase difference. Multiple measurements are repeated, and a middle result is selected after sorting. After the measurement is completed, the measurement circuit sends a voltage reduction command, and the variable frequency power supply slowly reduces the voltage to 0.
Precautions and Others
Precautions
1. This instrument can only be used on de-energized equipment; the grounding terminal should be reliably connected to the grounding grid,
and the instrument should be used in a spacious, safe, and reliable location as much as possible.
2. The equipment under test should be disconnected from the high-voltage line from the operating state to the maintenance state, cleaned, and after preliminary insulation tests are good, the instrument can be used for testing to prevent damage to the instrument during voltage application due to poor insulation of the equipment under test.
3. Determine which wiring method to use based on the installation situation of the equipment, and select the corresponding wiring method in the menu options.
4. Correctly select the test voltage level according to different equipment, and select the required voltage in the corresponding menu options.
5. If a special situation endangering safety occurs during the test, the main power can be turned off urgently.
6. Disconnect the power switch on the panel and clearly disconnect the 220V test power supply before changing wiring or ending work; when repeating tests on the same test equipment, press reset and measure again, or choose to repeat after the previous test is completed.
7. To ensure measurement accuracy, especially when the loss of small capacitance test objects is small, it is necessary to ensure that the low-voltage end (or secondary end) of the equipment under test has good insulation and measure in an environment with relatively low humidity.
8. When conducting experiments on large capacitance test objects, the grounding of the instrument and the grounding of the test object should not be at the same grounding point to prevent the impact of back voltage or traveling waves on the safety of the instrument during grounding discharge.
9. The instrument comes with a voltage boosting device; attention should be paid to the insulation distance of the high-voltage lead and personnel safety; 10、The instrument should be reliably grounded; poor grounding may cause machine protection or danger.
10. After the instrument is started, except for special circumstances, it is not allowed to suddenly turn off the power to avoid overvoltage damage to the equipment;
11. Although the special high-voltage wire (HVx) provided with the instrument has passed factory inspection, it still needs to be kept away from the human body and the low-voltage test line (Cx) during measurement; neither the high-voltage core wire nor the high-voltage shielding wire is allowed to be grounded or connected to the low-potential part of the test circuit.
The core wire and shielding wire of the CX input line are not allowed to contact the high-voltage part of the test circuit.
12. The instrument should be protected from moisture and severe vibration.
13. When the on-site interference is large and accurate results cannot be obtained with power frequency, the variable frequency measurement should be used; in other cases, power frequency measurement should be used.
14. If after issuing a measurement command, the measurement result does not appear on the screen for a long time (1 minute), it may be due to the test object capacitance being too large or a crash; restart the machine and lower the measurement voltage before measuring again.
15. A short circuit in the test object will prevent measurement, and the instrument will automatically protect itself. When a section extends from the paper outlet above the machine head, press the button to stop paper feeding. The printing paper is allowed to be pulled out.
Instrument Structure
Measurement circuit: performs all calculations such as Fourier transform, complex number operations, range switching, and variable frequency power supply control.
Control panel: printer, keyboard, display, and communication relay.
Variable frequency power supply: uses SPWM switching circuit to produce high-power sine wave regulated output.
Step-up transformer: boosts the output of the variable frequency power supply to the measurement voltage, with a maximum reactive power output of 2KVA/1 minute.
Standard capacitor: internal Cn, measurement reference.
Cn current detection: used to detect the current of the internal standard capacitor, 10μA~1A. Input resistance <2Ω.
Cx positive wiring current detection: only used for positive wiring measurement, 10μA~1A. Input resistance <2Ω.
Cx reverse wiring current detection: only used for reverse wiring measurement, 10μA~1A. Input resistance <2Ω.
Reverse wiring digital isolation communication: uses a precision MPPM digital modulation demodulator to transmit the reverse wiring current signal.


