Executive Standard: DL/T849.6-2004
XGTF Series Cable Variable Frequency Series Resonance Withstand Voltage Device Product Features:
● Cables with voltage levels of 35kV and below are used in large quantities, and the testing workload is heavy. Therefore, this type of withstand voltage test device is small in size, light in weight, and portable, which led to the creation of the portable cable withstand voltage test system.
● This system requires that the weight of any single component that can be moved on-site by one person does not exceed 30kg, making it suitable for on-site handling.
● The power supply uses 220V single-phase or 380V single-phase, making it convenient to obtain power on-site.
● The reactor part adopts dry-type epoxy casting, which is aesthetically pleasing and reliable, suitable for various cable requirements.
XGTF Series Cable Variable Frequency Series Resonance Withstand Voltage Device Technical Parameters:
● Rated output voltage: 0~66kV (RMS) and below
● Output frequency: 20~300Hz
● Resonant voltage waveform: sine wave, with waveform distortion rate ≤1%
● Full load working time: continuous working time 60min
● System quality factor: ≥20 at maximum load
● Frequency adjustment: fineness 0.1Hz, instability ≤0.01%
● Working power supply: 220V or 380V single-phase mains


