Scope of Application: Unless otherwise specified, the 10kV cable length given in the table above is under 2.0 times withstand voltage, at 32Hz~300Hz. If it is 2.5 times withstand voltage, at 39Hz~300Hz, the cable length should be reduced by 33% accordingly.

Product Configuration Instructions: 1. Users can optionally configure compensation capacitors.

2. Special test objects can be customized.

Common Models


0-44/22, capacity 44KVA, voltage 22KV

I. Cable AC Withstand Voltage Test Series

































Model Test Items Satisfied Reactor Configuration Remarks
DFVF3000-44/22 10kV (300mm) cable 1KM 22kV x 1 unit Portable
DFVF3000-132/66 1. 10kV (300mm) cable 3KM

2. 35kV (300mm) cable 1KM
22kV x 3 units Portable
DFVF3000-264/52 1. 10kV (300mm) cable 5KM

2. 35kV (300mm) cable 2KM

3. 35kV transformers, switches,

4. 10kV motors, transformers

5. Generators up to 600MW, etc.
22kV x 6 units Portable
DFVF3000-1560/66 110kV (300mm) cable 3KM 130kV x 2 units Non-portable

II. Generator Power Frequency Withstand Voltage Test Series




























Model Test Items Satisfied Reactor Configuration Remarks
DFVF3000-44/22 1. Generators up to 100MW, phase capacitance 0.1-0.3uF

2. 10kV (300mm) cable 1KM
22kV x 1 unit Portable
DFVF3000-100/36 1. Generators up to 600MW, phase capacitance 0.1-0.25uF

2. 10kV (300mm) cable 1.5KM
18kV x 2 units Portable
DFVF3000-176/44 1. Generators up to 600MW, phase capacitance 0.1-0.3uF

2. 10kV (300mm) cable 3KM 3. Can also cover generator busbars, main transformers, etc.
22kV x 4 units Portable

III. GIS and SF6 Switch AC Withstand Voltage Test Series






















Model Test Items Satisfied Reactor Configuration Remarks
DFVF3000-250/200 1. AC withstand voltage test for 110kV GIS

2. 35kV (300mm) cable 1KM

3. 10kV (300mm) cable 3KM

4. Power frequency withstand voltage for transformers below 220kV 5. AC withstand voltage for 110kV instrument transformers
40kV x 5 units Portable
DFVF3000-100/200 1. AC withstand voltage test for 110kV GIS 2. AC withstand voltage for 110kV instrument transformers 50kV x 4 units Portable

IV. Power Frequency AC Withstand Voltage Test Series for Transformers, Motors, etc.






















Model Test Items Satisfied Reactor Configuration Remarks
DFVF3000-105/84 1. Power frequency withstand voltage test for 110kV transformers

2. Power frequency withstand voltage test for 10kV motors 3. AC withstand voltage test for 35kV switches

4. 10kV (300mm) cable 1KM
28kV x 3 units Portable
DFVF3000-100/80 1. Power frequency withstand voltage test for 110kV transformers

2. Power frequency withstand voltage test for 10kV motors 3. AC withstand voltage test for 35kV switches

4. 10kV (300mm) cable 1KM
40kV x 2 units Portable

(Note: The above only lists some common models; customization is available upon request.)