SLQ-2000A Intelligent Three-Phase High Current Generator Manufacturer
SLQ-2000A Intelligent Three-Phase High Current Generator manufacturer/price is similar to that of high-voltage current transformers. Essentially, it is a double-winding step-down transformer.
Theoretically, the power on the primary and secondary sides is equal, and during operation, the voltage and current on the primary and secondary sides are inversely proportional. As a result, the voltage is reduced while the load current is increased.
The DC high voltage generator product is a new type of equipment, controlled by a chip, mainly selected based on your requirements for maximum current and load time.
After the high current generator (current booster) is connected to the working power supply, the output voltage of the voltage regulator is adjusted to obtain the large current required for the test.
SLQ-2000A Intelligent Three-Phase High Current Generator Main Technical Parameters:
| Model |
Rated Capacity (KVA) | Current Booster Rated Input | Current Booster Rated Output | Impedance Voltage% |
No-load Current% |
Structure Form |
|||
| Voltage Regulator | Current Booster | Current (A) | Voltage (V) | Current (KA) | Voltage | ||||
| SLQ-500A | 3 | 3 | 12 | 200 | 0.5 | 8 | ∠8 | ∠6 | Integrated |
| SLQ-1000A | 5 | 5 | 20 | 200 | 1 | 8 | ∠8 | ∠6 | Integrated |
| SLQ-2000A | 7.5 | 7.5 | 30 | 200 | 2 | 7 | ∠8 | ∠6 | Integrated |
| SLQ-3000A | 15 | 15 | 37.5 | 400 | 3 | 6 | ∠8 | ∠6 | Split |
| SLQ-4000A | 20 | 20 | 50 | 400 | 4 | 6 | ∠8 | ∠6 | Split |
| SLQ-5000A | 25 | 25 | 62.5 | 400 | 5 | 6 | ∠8 | ∠6 | Split |
| SLQ-6000A | 30 | 30 | 75 | 400 | 6 | 6 | ∠8 | ∠6 | Split |
| SLQ-8000A | 45 | 45 | 112.5 | 400 | 6 | 6 | ∠8 | ∠6 | Split |
| SLQ-10000A | 45 | 45 | 112.5 | 400 | 6 | 6 | ∠8 | ∠6 | Split |
SLQ-2000A Intelligent Three-Phase High Current Generator Usage Method:
1. According to the debugging requirements, connect the current booster and the test object, and connect the power supply.
2. Select the position of the current conversion switch based on the required current of the test object. Since the current transformer does not allow open circuit, the current conversion switch can only be set to "High" or "Low" position, and cannot be placed in the middle position.
3. Close the power supply, the green light turns on (if the green light does not turn on, turn the voltage regulator knob counterclockwise to zero until the green light turns on), press the start button, the green light turns off and the red light turns on, rotate the voltage regulator handle clockwise to raise the current to the required value.
4. Turn the voltage regulator handle counterclockwise to zero, press the stop button, the red light turns off and the green light turns on, the test ends.