CT-PT Transformer Volt-Ampere Characteristic Tester
Technical Specifications
3.1 Volt-Ampere Characteristic Technical Specifications:
|
Input Voltage |
Output Range |
Measurement Range |
Measurement Accuracy |
|
|
Main Unit |
220V |
0~550V, 0~20A |
0~550V, 0~20A |
< =0.5% |
|
Main Unit |
380V |
0~950V, 0~20A |
0~950V, 0~20A |
< =0.5% |
|
External Booster |
220V |
0~2000V, 0~3A |
0~2000V, 0~3A |
< =0.5% |
|
External Voltage Regulator |
0~1000V, 0~30A |
< =0.5% |
|
Device Operating Power Supply |
AC 220V±10%, 50/60Hz |
Operating Environment Temperature |
-10℃ - +50℃ |
|
Measurement Power Source |
AC 220V or AC 380V |
Dimensions, Weight |
420×300×270mm3, 34.5Kg |
3.2 Current Transformer Measurement Range:
Transformation Ratio: 5A/5A~25000A/5A (5A/1A~5000A/1A).
Turn Ratio Error: 1%.
3.3Voltage Transformer Measurement Range:
2.2kV~132kV, Measurement Error: Ratio Error 0.5 class.
3.4 Actual Secondary Load Test
PT Load 10VA~500VA, Measurement Error: Class 2
CT Load 0.1Ω~25Ω, Measurement Error: Class 2
3.5-inch Operating Conditions:
Power Supply Voltage: AC 220V ±10%
Power Frequency: 50Hz ±2%
Ambient Temperature: (0~40)℃
Ambient Humidity: <85% at 25℃
Features:
1. Fewer wiring terminals, simple wiring method, convenient for users.
2. Single-unit volt-ampere characteristic test output voltage 0-1000V, current 0-15A; single-unit transformation ratio test maximum output current 0-600A.
3. Fully automatic voltage boosting, current boosting, plotting volt-ampere characteristic curves, CT-PTTransformer Volt-Ampere Characteristic Tester calculates transformation ratio results, saving tedious manual voltage adjustment, manual recording, curve plotting and other labor, improving work efficiency.
4. Can simulate test transformer angle error and ratio error without external standard transformer and voltage/current source.
5. Can test CT/PT volt-ampere characteristics, transformation ratio, polarity, angle error, ratio error, 5%, 10% error curves, secondary side loop, secondary AC withstand voltage and demagnetization experiments.
6. Large screen Chinese LCD display, intuitive and convenient.
7. Built-in micro fast printer, can print curve charts and test data on site.
8. Uses imported photoelectric rotary encoder, simple and convenient operation.
9. Large capacity memory, can save 1000 sets of test data, not lost on power failure.
10. USB communication interface, can connect to laptop for testing.
11. Small size, light weight, convenient for mobile testing.
Technical Specifications:
1. Input Voltage: AC 220V or 380V, 50HZ, automatic identification of input voltage.
2. Operating Environment Temperature: 0~40℃
3. Output Voltage:
When input AC 220V, output 0~550V;
When input AC 380V, output 0~1000V.
Current: maximum instantaneous current when measuring transformation ratio is 240A
When testing volt-ampere characteristics is 15A.
4. Digital Voltmeter Measurement Range: 0~999.9V; Resolution: 0.1V.
When used as current display: 0~999.9mA; Resolution: 0.1mA.
5. Digital Ammeter Measurement Range: 0~15A (240A), Resolution: 0.01A.
6. Error: I≤3%, U≤3%.
7. When measuring CT transformation ratio, can automatically calculate transformation ratio value, and print data and calculation results.
8. When measuring volt-ampere characteristics, store and print 20 sets of current and voltage values and volt-ampere characteristic curves.
9. External Dimensions: Length×Width×Height = 470×340×260mm3
10. Weight: 21kg.