High Voltage Circuit Breaker Characteristic Tester Instrument Features
◆Strong anti-interference capability, fully adaptable to on-site testing at high-voltage substations.
◆High-grade safety case integrated chassis, preventing possible damage during transportation and use.
◆3x4 channels for time measurement, with independent channel timing and time resolution up to 0.05ms. 6 digital channels for measurement, and 6 digital/analog (with closing resistor) channels with automatic identification.
◆Full Chinese operation interface, wide-temperature semi-transmissive LCD display, real-time display of all contact states.
◆Patented dynamic key attribute design and interface layout, making human-machine interaction simple, clear, and efficient.
◆The instrument automatically identifies the target close/open state and selects the corresponding test mode, making operation simple and convenient.
◆The instrument comes with an adjustable operating power supply from 20A, 20V to 280V, with low ripple factor; only 220V AC is needed on-site for various tests.
◆The instrument provides energy storage function for the switch through its internal DC operating power supply.
◆Supports external power input; when the 20A power supply is insufficient for on-site needs, an external DC operating power supply can be connected, and the internal power supply automatically shuts off.
◆Fully automatic low-voltage test; only need to set the starting voltage value, and the test process can be completed without manual intervention.
◆High-speed thermal printer for quick storage of test results.
◆Real-time wiring error check function to prevent user wiring errors that could damage the instrument or the device under test.
◆Reclosing test can measure metal short-circuit and no-current time in one go.
◆Supports linear and angular velocity measurement, suitable for vacuum, low-oil, multi-oil, SF6, load, GIS, etc., from 6KV to 750KV.
◆Dynamic parameter testing of switches, with test results available for in-depth analysis.
◆Automatic identification and switching between internal and external synchronization, supporting time testing of AC load switches.
◆Stores 16 sets of measurement data and waveforms locally; unlimited storage when a USB drive is connected, with optional automatic USB storage function.
◆Provides LAN connection to PC; optional professional PC analysis software for precise analysis of test data.
◆Excellent electromagnetic compatibility design ensures stable operation in substations of 500kV and above; wiring short-circuit protection and robust output arc suppression design ensure equipment and personnel safety under abnormal conditions.
High Voltage Circuit Breaker Characteristic Tester Technical Specifications
|
Test Item |
Range |
Resolution |
Accuracy |
|
Time Measurement |
Internal sync: <2S External sync: >1S |
0.05ms |
0.05% reading ±0.05ms |
|
Travel Measurement |
0~900mm |
0.05mm |
0.01% |
|
Speed Measurement |
0~30m/s |
0.01m/s |
Reading ±0.1m/s |
|
Reclosing Measurement |
>20ms |
0.05ms |
0.05% reading ±0.05ms |
|
Opening/Closing Current Measurement |
0~30A |
20mA |
5% |
|
Closing Resistor Measurement |
10 ohm~1000 ohm |
0.5 ohm |
5% |
Other Specifications:
Operating Power: AC 220V
Number of Test Contacts: 6 normal contacts + 6 contacts with closing resistors
Travel Sensor: 1 photoelectric encoder, optional resolution up to 5000 points
DC Operating Voltage Range: 20V-280V, max current 20A
External Power Input: max operating current 30A
Energy Storage Motor Drive: 48V-220Vdc, 10A
Printer: 24-dot matrix high-speed thermal printer
Computer Interface: Ethernet (LAN) + USB port
Storage Capacity: 16 sets of measurement data and waveforms stored locally; unlimited storage when USB drive is connected
Display: 320×240 black and white LCD (visible in strong outdoor light)
Operating Environment: -20℃~+55℃
Relative Humidity: ≤90%
Dimensions: 37cm X 30cm X 15cm
Weight: 4KG
Operating Environment
Input Power 220V±10% 50Hz±10% Atmospheric Pressure 86~106kPa
Temperature -20~45℃ Humidity ≤80%RH
3.2 Safety Performance
Insulation Resistance >2.0MΩ
Dielectric Strength Power supply to chassis: 1.5KV for 1 minute, no flashover or arcing.
3.3 Basic Parameters
◆Time: Range 0-64000.0ms Resolution 0.1ms Error ≤ 0.1%rdg±0.1
◆Speed: Range 0-20.00m/s Resolution 0.01m/s Error ≤1%rdg±0.01