The high-current generator is essential equipment for power maintenance departments

The high-current generator is essential equipment for power maintenance departments




 

 It is necessary equipment for places requiring high current in electrical debugging across various industries. It is applied in power plants, substations, electrical appliance manufacturing plants, and scientific research and laboratory units. It belongs to short-time or intermittent duty systems; increasing the current-carrying time can improve work efficiency and expand the testing range. It features small size, light weight, good performance, and convenient use and maintenance.

  The high-current generator is necessary equipment for places requiring high current in debugging within the power and electrical industries. This device has the characteristics of convenient use and maintenance, superior performance, safe and reliable use, beautiful appearance, sturdy and durable structure, and easy mobility. It is essential equipment for power supply enterprises, large factories, metallurgy, power plants, railways, and other power maintenance departments. It adopts advanced microelectronic processing technology, and the entire process can be set in advance, with a full Chinese interface and simple and clear operation. After setting all test items, the test is automatically performed without manual intervention. Through optimization and upgrading of structure, electrical performance, materials, and processes, it can improve current-carrying time, current stability, and the ratio of volume and weight to power.

  The high-current generator uses imported high-permeability materials, is exquisitely designed, and has the characteristics of small size, strong electric dynamic resistance, and convenient use. This series of high-current generators is necessary equipment for places requiring high current in electrical debugging across various industries. It is suitable for current load tests and temperature rise tests of 50HZ switches, current transformers, and other electrical equipment. After power failure, there is no need to reset to zero and adjust again; the test can be continued.

  Use and maintenance of the high-current generator

  1. Check whether the main circuit wiring terminals are loose and whether the voltage regulator brush is in good contact.

  2. If not used for a long time, before use, use a 500V megohmmeter to check the insulation resistance of the main circuit to ground, which should not be less than 0.5 megohms.

  3. The input voltage should conform to the voltage value indicated on the nameplate, with a difference within ±10%, and the frequency should be 50HZ.

  4. The current gear switch is not allowed to be operated under load.

  5. During operation, the handwheel should be rotated evenly and slowly to avoid damaging the voltage regulator.

  6. At full load, the working time should not exceed 5 minutes, and the continuous working time should be less than 2.5 minutes, but the working cycle should be greater than 10 minutes.

  7. The current generator casing has a grounding terminal, and it should be properly grounded during use.