CT-PT Transformer Volt-Ampere Characteristic Tester



Technical Specifications



3.1 Volt-Ampere Characteristic Technical Specifications:









































 

Input Voltage



Output Range



Measurement Range



Measurement Accuracy



Main Unit



220V



0~550V, 0~20A



0~550V, 0~20A



< =0.5%



Main Unit



380V



0~950V, 0~20A



0~950V, 0~20A



< =0.5%



External Booster Transformer



220V



0~2000V, 0~3A



0~2000V, 0~3A



< =0.5%



External Voltage Regulator


   

0~1000V, 0~30A



< =0.5%




















Device Operating



Power Supply



AC 220V±10%, 50/60Hz



Operating Environment



Temperature



-10℃ - +50℃



Measurement



Power Source



AC 220V or AC 380V



Dimensions, Weight



420×300×270mm3, 34.5Kg




3.2 Current Transformer Measurement Range:



Transformation Ratio: 5A/5A~25000A/5A (5A/1A~5000A/1A).



Turn Ratio Error: 1%.



3.3Voltage Transformer Measurement Range:



2.2kV~132kV, Measurement Error: Ratio error 0.5 class.



3.4 Actual Secondary Load Test



PT Load 10VA~500VA, Measurement Error: Class 2



CT Load 0.1Ω~25Ω, Measurement Error: Class 2



3.5-inch Operating Conditions:



Power Supply Voltage: AC 220V ±10%



Power Frequency: 50Hz ±2%



Ambient Temperature: (0~40)℃



Ambient Humidity: <85% at 25℃



Features:



1. Fewer wiring terminals and simple wiring method for user convenience.



2. Standalone volt-ampere characteristic test output voltage 0-1000V, current 0-15A; standalone transformation ratio test maximum output current 0-600A.



3. Fully automatic voltage and current boosting, plotting of volt-ampere characteristic curves, CT-PT Transformer Volt-Ampere Characteristic Tester calculates transformation ratio results, eliminating tedious manual voltage adjustment, manual recording, and curve plotting, improving work efficiency.



4. Can simulate and test transformer angle error and ratio error without external standard transformers and voltage/current sources.



5. Can test CT/PT volt-ampere characteristics, transformation ratio, polarity, angle error, ratio error, 5% and 10% error curves, secondary circuit, secondary AC withstand voltage, and demagnetization tests.



6. Large Chinese LCD display, intuitive and convenient.



7. Built-in high-speed micro printer for on-site printing of curve graphs and test data.



8. Uses imported photoelectric rotary encoder for simple and convenient operation.



9. Large capacity memory, can store 1000 sets of test data, data not lost on power failure.



10. USB communication interface, can connect to a laptop for testing.



11. Compact size and light weight, convenient for mobile testing.



Technical Specifications:



    1. Input Voltage: AC 220V or 380V, 50Hz, automatic input voltage recognition.

    2. Operating Ambient Temperature: 0~40℃

    3. Output Voltage:

        When input AC 220V, output 0~550V;

        When input AC 380V, output 0~1000V.

        Current: maximum instantaneous current for transformation ratio test is 240A

      For volt-ampere characteristic test is 15A.

    4. Digital Voltmeter Measurement Range: 0~999.9V; Resolution: 0.1V.

                          When used as current display: 0~999.9mA; Resolution: 0.1mA.

    5. Digital Ammeter Measurement Range: 0~15A (240A), Resolution: 0.01A.

    6. Error: I≤3%, U≤3%.

    7. When testing CT transformation ratio, can automatically calculate the ratio value, and print the data and calculation results.

    8. When testing volt-ampere characteristics, stores and prints 20 sets of current and voltage values and the volt-ampere characteristic curve.

    9. External Dimensions: Length×Width×Height = 470×340×260mm3

   10. Weight: 21kg.