Power Testing Level III/DC Resistance Tester
After the transformer is handed over, overhauled, and the tap changer is changed, it is an indispensable test item. In normal circumstances, using traditional methods (bridge method and voltage drop method) to measure transformer windings and the DC resistance of high-power inductive equipment is a time-consuming and labor-intensive task. To change this situation, shorten measurement time, and reduce the workload of test personnel, our company has developed the 40A DC Resistance Rapid Tester (hereinafter referred to as the DC Resistance Tester). It adopts new power supply technology and has the characteristics of stable performance, rapid measurement, compact size, convenient use, high measurement accuracy, and good data repeatability. It is an ideal device for measuring the DC resistance of transformer windings and high-power inductive equipment.
This product complies with the requirements of DL/T845.3-2004, the national standard GB6587 "General Outline for Environmental Testing of Electronic Measuring Instruments," and GB6593 "Rules for Quality Inspection of Electronic Instruments."
Product Features:
1. Can stably output 40A DC current, fast and stable testing
2. Large-capacity CPU can store 255 sets of measurement results
3. Large-screen LCD display, full Chinese menu-guided operation, intuitive and simple
4. This DC resistance rapid tester has automatic discharge and discharge indication functions, reducing misoperation and ensuring the safety of equipment and personnel
5. Large output current, light weight, vertical chassis, convenient for on-site use
6. Comes with a panel-mounted micro printer, can print measurement results in Chinese
7. Power Testing Level III/DC Resistance Tester, stored results can be viewed and printed
Instrument Technical Specifications:
1. Output four gear currents: 40A, 20A, 10A, 5A
2. Resolution: 0.1μΩ
3. Range: 20mΩ - 4Ω (5A gear); 10mΩ - 2Ω (10A gear);
0.2mΩ - 1Ω (20A gear); 0.1mΩ - 0.5Ω (40A gear);
4. Accuracy: 0.2%
5. Ambient temperature: 0~40℃
6. Ambient humidity: <90%RH
7. Working power supply: AC220V±10%, (50±1)HZ
8. Dimensions: 400×200×350mm
9. Weight: 13kg
Daily Maintenance of the Instrument:
1. Within three months, if the instrument fails to meet technical requirements due to its own reasons, it can be replaced unconditionally.
2. Free repair within one year, and lifelong maintenance and technical service are provided.
3. If the instrument has quality problems, a maintenance plan will be proposed on the same day, and on-site handling will be carried out promptly. Alternative instruments can also be provided to meet user needs.
4. Free on-site technical support and training on instrument usage knowledge are provided.
5. If the instrument malfunctions, please contact us promptly so that we can provide you with service.![]()